RS485 DF1 Module Parameters
B-7
Sets the data that is sent to the Datalink in the drive if module
parameter 10 (Comm Flt Action) is set to “Send Flt Cfg” and
communications are disrupted.
Important: If the drive uses a 16-bit Reference, the most significant
word of this value must be set to zero (0) or a fault will
occur.
Selects the method of error detection for data communications. This
setting must match the method used by the software or controller
communicating with the module.
Displays the actual method of error detection used.
16
17
18
19
20
21
22
23
Flt Cfg A1
Flt Cfg A2
Flt Cfg B1
Flt Cfg B2
Flt Cfg C1
Flt Cfg C2
Flt Cfg D1
Flt Cfg D2
Range:
0 to 4294967295
Default:
0
Type:
Read/Write
Reset Required: No
24
CRC/BCC Cfg
Range:
0 = BCC (Block Check Character)
1 = CRC (Cyclic Redundancy Check)
Default:
0 = BCC
Type:
Read/Write
Reset Required: Yes
25
CRC/BCC Act
Range:
0 = BCC (Block Check Character)
1 = CRC (Cyclic Redundancy Check)
Default:
0 = BCC
Type:
Read Only
Reset Required: N/A