Rockwell Automation RECOMM-485 RS485 DFI Communications Module User Manual

Page 52

Advertising
background image

B-6

RS485 DF1 Communications Module

Displays the I/O that the module is actively transmitting. The value
of this parameter will usually be equal to the value of module
parameter 12 (DPI I/O Cfg). See figure B.2.

Sets the Logic Command data that is sent to the drive if module
parameter 10 (Comm Flt Action) is set to “Send Flt Cfg” and
communications are disrupted.

The bit definitions will depend on the product to which the module is
connected.

Sets the Reference data that is sent to the drive if module
parameter 10 (Comm Flt Action) is set to “Send Flt Cfg” and
communications are disrupted.

Important: If the drive uses a 16-bit Reference, the most significant

word of this value must be set to zero (0) or a fault will
occur.

13

DPI I/O Active

Range:

See figure B.2.

Default:

xxx0 0001

Type:

Read Only

Reset Required: N/A

Figure B.2 – DPI I/O Active (Parameter 13)

0

0

0

1

0

x

x

x

0

1

2

3

4

5

6

7

1 = I/O Enabled
0 = I/O Disabled
x =Not Used

Cmd/Ref

Datalink A

Datalink B

Datalink C

Datalink D

Not Used

Not Used

Not Used

14

Flt Cfg Logic

Range:

0000 0000 0000 0000 to 1111 1111 1111 1111

Default:

0000 0000 0000 0000

Type:

Read/Write

Reset Required: No

15

Flt Cfg Ref

Range:

0 to 4294967295

Default:

0

Type:

Read/Write

Reset Required: No