Rockwell Automation RECOMM-485 RS485 DFI Communications Module User Manual
Page 52

B-6
RS485 DF1 Communications Module
Displays the I/O that the module is actively transmitting. The value
of this parameter will usually be equal to the value of module
parameter 12 (DPI I/O Cfg). See figure B.2.
Sets the Logic Command data that is sent to the drive if module
parameter 10 (Comm Flt Action) is set to “Send Flt Cfg” and
communications are disrupted.
The bit definitions will depend on the product to which the module is
connected.
Sets the Reference data that is sent to the drive if module
parameter 10 (Comm Flt Action) is set to “Send Flt Cfg” and
communications are disrupted.
Important: If the drive uses a 16-bit Reference, the most significant
word of this value must be set to zero (0) or a fault will
occur.
13
DPI I/O Active
Range:
See figure B.2.
Default:
xxx0 0001
Type:
Read Only
Reset Required: N/A
Figure B.2 – DPI I/O Active (Parameter 13)
0
0
0
1
0
x
x
x
0
1
2
3
4
5
6
7
1 = I/O Enabled
0 = I/O Disabled
x =Not Used
Cmd/Ref
Datalink A
Datalink B
Datalink C
Datalink D
Not Used
Not Used
Not Used
14
Flt Cfg Logic
Range:
0000 0000 0000 0000 to 1111 1111 1111 1111
Default:
0000 0000 0000 0000
Type:
Read/Write
Reset Required: No
15
Flt Cfg Ref
Range:
0 to 4294967295
Default:
0
Type:
Read/Write
Reset Required: No