Troubleshooting the Module and Network
6-3
6.1.2 MS Status Indicator
Table 6.2 – MS Status Indicator: State Definitions
Status
Cause
Corrective Action
Off
The module is not
powered.
•
Securely connect the module
to the SP600 drive using the
Internal Interface cable.
•
Apply power to the drive.
Flashing
Red
The module has
failed the firmware
test.
•
Clear faults in the module.
•
Cycle power to the drive.
•
If cycling power does not
correct the problem, the
parameter settings may have
been corrupted. Reset defaults
and reconfigure the module.
•
If resetting defaults does not
correct the problem, flash the
module with the latest firmware
release.
Solid
Red
The module has
failed the hardware
test.
•
Cycle power to the drive.
•
Replace the module.
Flashing
Green
The module is
operational but is not
transferring I/O data.
•
Place the scanner in RUN
mode.
•
Program the controller to
recognize and transmit I/O to
the module.
•
Configure the module for the
program in the controller.
•
Normal behavior if no DPI I/O
is enabled.
Solid
Green
The module is
operational and
transferring I/O data.
•
No action required.