Ppendix, Logic command/ status words, C.1 sp600 drives – Rockwell Automation RECOMM-485 RS485 DFI Communications Module User Manual

Page 55

Advertising
background image

Logic Command/Status Words

C-1

A

PPENDIX

C

Logic Command/

Status Words

Appendix C provides the definitions of the Logic Command/Logic
Status words that are used for some products that can be
connected to the RS485 DF1 module. If you do not see the Logic
Command/Logic Status for the product that you are using, refer to
your product’s documentation.

C.1 SP600 Drives

Logic Command Word

Logic Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Command

Description

x Stop

0 = Not Stop
1 = Stop

x

Start

1

0 = Not Start
1 = Start

x

Jog

0 = Not Jog
1 = Jog

x

Clear Faults

0 = Not Clear Faults
1 = Clear Faults

x x

Direction

00 = No Command
01 = Forward Command
10 = Reverse Command
11 = Hold Direction Control

x

Local Control 0 = No Local Control

1 = Local Control

x

MOP
Increment

0 = Not Increment
1 = Increment

x x

Accel Rate

00 = No Command
01 = Accel Rate 1 Command
10 = Accel Rate 2 Command
11 = Hold Accel Rate

x

x

Decel Rate

00 = No Command
01 = Decel Rate 1 Command
10 = Decel Rate 2 Command
11 = Hold Decel Rate

Advertising