57

Calibration

IMPORTANT

: Calibrate the TACH VOLTS setting only

when a tachometer is used. The TACH VOLTS setting, like
the IR COMP setting, determines the degree to which the
motor speed is held constant as the motor load changes.

To calibrate the TACH VOLTS trimpot:
1. Disconnect power from drive.
2. Connect the tachometer to T1 and T2. The polarity

is (+) for T1 and (-) for T2 when the motor is running in
the forward direction.

TACH VOLTS

ATTENTION:

Applying the incorrect polarity to the

tachometer can cause an overspeed condition. Make
sure the positive (+) wire is connected to terminal T1
and the negative (-) wire is connect to terminal T2 when
the motor is running in the forward direction. Failure to
observe this precaution could result in bodily injury.

ATTENTION:

The control circuit is at line potential

when the drive is energized. Use a non-metallic
screwdriver when making adjustments to the circuit
board potentiometers. Exercise extreme caution as
hazardous voltage exists. Failure to observe these
precautions could result in severe bodily injury or loss
of life.

ƽ

250-0287-rev2.qxd

3/12/01

10:27 AM

Page 57