PSU Configuration

Dynamic PSU

Engagement

Firmware Response

Power Supply

Redundancy

Enabled

CMC alerts you of loss of Power Supply Redundancy. PSUs in

standby mode (if any) are turned on to compensate for power

budget lost from PSU failure or removal.

No Redundancy

Enabled

Decrease power to low priority servers, if needed.

Power Supply and Redundancy Policy Changes in System Event Log

Changes in the power supply state and power redundancy policy are recorded as events. Events related to the power
supply that record entries in the system event log (SEL) are power supply insertion and removal, power supply input
insertion and removal, and power supply output assertion and de-assertion.
The following table lists the SEL entries that are related to power supply changes:

Table 40. SEL Events for Power Supply Changes

Power Supply Event

System Event Log (SEL) Entry

Insertion

Power supply <

number

> is present.

Removal

Power supply <

number

> is absent.

Grid or Power Supply Redundancy lost

Power supply redundancy is lost.

Grid or Power Supply Redundancy regained

The power supplies are redundant.

Input power received

The input power for power supply <

number

> has been restored.

Input power lost

The input power for power supply <

number

> has been lost.

DC output produced

Power supply <

number

> is operating normally.

DC output lost

Power supply <

number

> failed.

Input over-voltage

An over voltage fault detected on power supply <

number

>.

Input under-voltage

An under voltage fault detected on power supply <

number

>.

Input over-current

An over current fault detected on power supply <

number

>.

Input under-current

An undercurrent fault detected on power supply <

number

>.

DC output under-voltage

An output under voltage fault detected on power supply <

number

>

DC output over-current

An output over current fault detected on power supply <

number

>.

DC output under-current

An output under current fault detected on power supply <

number

>.

Communication failure

Cannot communicate with power supply <

number

>.

Communication restored

Communication has been restored to power supply <

number

>.

Failure to communicate status data

Cannot obtain status information from power supply <

number

>.

Status data communication restored

Power supply <number> status information successfully obtained.

Over/Under-temperature

The temperature for power supply <

number

> is outside of range.

Fan or Airflow error/warning

Fan failure detected on power supply <

number

> .

Fan speed overridden

Fan failure detected on power supply <

number

> .

Manufacturing fault

Power supply <

number

> failed.

Microprocessor busy

Power supply <

number

> failed.