Dell POWEREDGE M1000E User Manual

Page 259

Advertising
background image

– Allow 110 VAC Operation.

Selecting the check box to enable Server Based Power Management (SBPM), displays the following message:
Checking the Server Based Power Management Mode option will set your power

cap to max value, server priorities to default priority, and disables Max

Power Conservation Mode. Are you sure you want to continue?

Selecting the check box to enable Max Power Conservation Mode (MPCM), displays the following message:
Enabling Max Power Conservation Mode option will force servers into a low

power, limited performance mode and disable server power up. Press OK to

continue.

Scenario 3: The EPP option is grayed out and not available for selection, if:

EPP is disabled with 3000W PSUs, and any of the following power settings is enabled:

– Server Based Power Management (SBPM)
– Redundancy Policy: Power Supply Redundancy or No Redundancy
– Max Power Conservation Mode (MPCM).
– Dynamic Power Supply Engagement (DPSE).
– System Input Power Cap is set to value less than or equal to 13300W or (45381 BTU/h) .

The chassis does not have six 3000W PSUs or all the PSUs do not support EPP , the EPP option is grayed out and not

available for selection.

Extended Power Performance Scenarios - Using RACADM

Scenario 1: Managing EPP feature control (enable/disable) using racadm getconfig/config set commands

To enable EPP feature on a 3000W AC PSU configuration, use:
racadm config -g cfgChassisPower -o cfgChassisEPPEnable 1

To disable EPP feature on a 3000W AC PSU configuration, use:
To disable EPP feature on a 3000W AC PSU configuration, use:

To verify if the EPP feature is enabled on a 3000W AC PSU configuration, use:
racadm getconfig -g cfgChassisPower -o cfgChassisEPPEnable

Scenario 2: Viewing EPP feature status using racadm getpbinfo:
racadm getpbinfo

Extended Power Performance(EPP) Status = Enabled (inactive)

Available Power in EPP Pool = 3167 W (10806 BTU/h)

Used Power in EPP Pool = 0 W (0 BTU/h)

EPP Percent - Available = 100.0

Scenario 3: Viewing EPP feature control operations recorded in CMC logs:
racadm getraclog

Jul 31 14:16:11 CMC-4C2WXF1 Log Cleared

Jul 31 14:15:49 CMC-4C2WXF1 Extended Power Performance is Enabled

Jul 31 14:15:49 CMC-4C2WXF1 Extended Power Performance is Disabled

Scenario 4: Changing Power configuration properties that are incompatible with EPP, when EPP is enabled:

Enabling Server Based Power Mangement (SBMP) on a 3000W AC PSU
racadm config -g cfgChassisPower -o cfgChassisServerBasedPowerMgmtMode 1

This feature is not supported while Extended Power Performance is enabled.

Enabling Dynamic Power Supply Engagement on a 3000W AC PSU
racadm config -g cfgChassisPower -o cfgChassisDynamicPSUEngagementEnable 1

This feature is not supported while Extended Power Performance is enabled.

259