Installing System Components | 89


Power Supplies

NOTE: The following table lists the maximum supported configuration where
power supply redundancy is guaranteed.

NOTE: Configurations higher than indicated in the table may change the
power supply mode to non-redundant. In non-redundant mode if the power
requirement exceeds the installed system power capacity, the BIOS will
throttle the CPUs. Also, if CPU Power Capping is enabled, then CPU
throttling occurs on configurations that exceed the cap value.

Table 3-1. PSU and System Board Support Matrix
PSU

Two System Boards

Four System Boards

1400W

Full configuration*

Up to two 95W processors /
MLB, two hard drives / MLB, and
four memory modules / MLB

1100W

Full configuration*

Up to two 65W processors /
MLB, one hard drives / MLB, and
six memory modules / MLB

750W

Up to two 95W processors / MLB,
two hard drives / MLB, and four
memory modules / MLB

N/A

470W

Up to two 35W processors / MLB,
up to one hard drives / MLB, and
three memory modules / MLB

N/A