NOTE: The suction line should be clamped near the inlet end of the vibration
eliminator. The vibration eliminator is located between the clamp and the
compressor

.

注:该吸入管路应靠近振动消除器的入口端应被夹紧。

振动消除器位于所述夹钳与压缩机之间。


Split System Interconnecting Line Sizing Chart

分体式系统互连管线尺寸图

Table 3

Model

Liquid
Line(OD
mm)

Liquid
connection
at
evaporator
(OD) mm

Suction
line (OD)

Min.
Suction
line
insulation
thickness
mm

Suction
connection
at
evaporator
(OD) mm

Maximum
“total” line
length
mm

Maximum
lift
(height)
mm

WGS40

6

6

10

10

10

18

5

WGS75

6

6

12

10

6

18

5

WGS100

10

6

12

16

12

18

5

WGS175

10

10

22

16

12

18

5

*Interconnecting tube must be reduced down at evaporator connection 连接管直径在蒸发器接口

处必须相应缩小

Notes:

Line lengths are expressed in equivalent feet = actual run length + fitting

allowances (i.e. ~5’ for each bend/elbow allowance).

Use only refrigeration grade dehydrated tubing.

Install refrigeration piping per local codes and ASHRAE guidelines.


注意事项:
•线路长度均以相当于英尺=实际运行长度+管接头允许误差(比如每个弯/肘津贴有〜5
英寸左右的误差)。
•请只能使制冷级的脱水油管。
•请根据当地法规和 ASHRAE 指引,安装制冷管道。