Problems controlling cellar temperature 酒窖温度控制问题 – Wine Guardian Ducted Split Wine Cellar Cooling Systems (WGS175) - Manual User Manual

Page 86

Advertising
background image

87

Power Switch Light is On and the Thermostat Light is On

电源开关指示灯亮起,恒温器灯亮

Possible Cause 可能的问题

Solution 解决方法


Thermostat is not set up properly Check thermostat set up in the guide.

检查温控器设置指南。

温控器设置不正确 Press fan ON switch to check evaporator fan
only.

按风扇开关,只检查蒸发器风扇。

Unit is Operating and Blows Evaporator Air, but the Supply Air is Not

Colder Than the Return Air from the Cellar

主机工作, 吹出蒸发器空气,但气源温度低于地窖里的回风空气

Possible Cause 可能的问题 Solution 解决方法

Thermostat not set up properly Check thermostat setup in the manufacture’s
温控器设置不正确 thermostat guide

检查温控器设置指南

Compressor not operating 压缩机不工作 High pressure switch open (button up)

高压开关打开

Condenser airflow is blocked Remove blockage 取除堵塞
冷凝器气流受阻 Clean filter and coil (if needed)

清洁过滤网和线圈(如需要)


Head Pressure (HP) switch is open Reset HP switch See reset instructions on
page 56
头压力开关打开 复位高压卡关。见 56 页。

Problems Controlling Cellar Temperature 酒窖温度控制问题

Problems are occurring even though the unit seems to be fully operational – evaporator fan blows
air into the cellar and compressor and condenser fan runs.

主机全面运行, 仍然有问题 - 蒸发器风扇向酒窖吹风,压缩机和冷凝器风扇运行

Cellar Temperature too cold (below 11°C) when unit is running
当设备运行时,酒窖温度太冷(低于 11 ° C


Possible Cause 可能的问题

Solution 解决方法