Setting the siemens simatic manager, Setting the siemens simatic manager -11 – KEYENCE IV Series User Manual

Page 69

Advertising
background image

5-11

- IV Series User’s Manual (Field Network) -

Data I/O communication setting method

Setting the Siemens SIMATIC Manager

This following explains the setting method when
using SIMATIC Manager.

1

Launch [SIMATIC Manager] with the PC

and CPU connected, and then select [New]

from the [File] menu.

2

Enter the project name into the [Name]

field, and then click the [OK] button.

3

Right click the project name in the Object

Hierarchy in [SIMATIC Manager], and then

select [Insert New Object] - [SIMATIC 300

Station].

[SIMATIC 300] will be added.

4

Expand [Object Hierarchy] and select

[SIMATIC 300], and then double-click

[Hardware].

The [HW Config] window will appear.

5

Expand [SIMATIC] - [RACK-300] from

[Hardware Catalog], and then drag & drop

[Rail] onto the Station Window.

“Rail” will be added to the Station window.

6

Drag & drop the CPU to be connected

from [Hardware Catalog] and add it to the

hardware configuration diagram.

The [Properties-Ethernet interface PN-IO]
window will appear.

5

Data I/O communication

Advertising