KEYENCE IV Series User Manual

Page 72

Advertising
background image

5-14

- IV Series User’s Manual (Field Network) -

Data I/O communication setting method

17

Select [Station] - [Save and Compile] in

the [HW Config] window, and save the

settings.

18

Select [PLC] - [Download] in the [HW

Config] window to download the settings

to the CPU.

19

Set the CPU mode switch to “RUN”.

If the connection is successful, the RUN LED
of the CPU will light in green and the data I/O
communication will become enabled.

y

By default, [Size of the process-image input
area] is set to “128”.
To be able to access the addresses after
address 128, expand the setting as shown
below.

y

Modifying [Size of the process-image input
area] may affect the scan time of the PLC.
Make sure to conduct a thorough verification
before the operation.

5

Data I/O communication

Advertising