AERCO RECON 1000 User Manual
Page 127
 
RECON Water Heaters Installation, Operation & Maintenance Manual
CHAPTER 8 – WATER HEATER MANAGEMENT
OMM-0103_0A
AERCO International, Inc.
 100 Oritani Dr.  Blauvelt, NY 10913
Page 127 of 178
GF-147
Phone: 800-526-0288 PRI:
10/28/2014
8.8.3 Control and Power Wiring
Control and power wiring connections to the sequencing valves associated with each C-More 
WHM unit is accomplished by simply ensuring that the 4-pin Molex connectors on the units are 
connected to the corresponding connectors on the valves. 
Figure 8-4 WHMS Network Wiring Diagram
NOTES:
Wiring to be shielded twisted-
pair cable (Belden 9841 or 
equivalent). 
 
Complete the following 
instructions: 
1. Activate DIP 1 (Modbus 
TERM) on the first and last 
units in the daisy chain. 
2. Tie incoming/outgoing
shields together and 
terminate at the shield 
terminal of the LAST WHMS 
slave in the chain. 
3. On the CPU board inside the
C-More Control Panel of the 
last unit on the chain, turn 
the DIP switches labeled 
BIAS1 and BIAS2 to the 
“ON” position.