3.10 START/STOP LEVELS

The start and stop levels are the Air/Fuel Valve positions (% open) that start and stop the unit,
based on load. These levels are Factory preset as follows:

Start Level

Stop Level

RECON 500

28%

16%

RECON 1000

25%

20%

Normally, these settings should not require adjustment.

Note that the energy input is not linearly related to the Air/Fuel Valve position. Refer to Table 3-
7 for the relationship between the energy input and Air/Fuel Valve position for a unit running on
natural gas.

Table 3-7: Relationship between Air/Fuel Valve Position and Energy Input

For Units Running Natural Gas

Air/Fuel Valve

Position (%

Open)

RECON Water Heater Model: Energy Input

(BTU/Hr.)

RECON 500

RECON 1000

16% 50,000

Not

Applicable

20% Not

Applicable 100,000

30% 116,100 188,000

40% 204,000 334,000

50% 268,700 485,000

60% 320,600 590,000

70% 367,200 693,000

80% 409,400 806,000

90% 448,500 954,000

100% 500,000 1,000,000