RECON Water Heaters Installation, Operation & Maintenance Manual

APPENDIX B – STARTUP, STATUS AND FAULT MESSAGES

OMM-0103_0A

AERCO International, Inc.

 100 Oritani Dr.  Blauvelt, NY 10913

Page 147 of 178

GF-147

Phone: 800-526-0288 PRI:

10/28/2014

TABLE B-2. FAULT MESSAGES – Continued

FAULT MESSAGE

FAULT DESCRIPTION

OUTDOOR TEMP
SENSOR FAULT

The temperature measured by the Outdoor Air Sensor is out
of range.

OUTLET TEMP
SENSOR FAULT

The temperature measured by the Outlet Sensor is out of
range:
OUTLET TEMPERATURE display = SHt Indicates sensor is
shorted
OUTLET TEMPERATURE display = OPn indicates sensor is
open-circuited

PRG SWTCH CLOSED
DURING IGNITION

The Purge Position Limit Switch on the Air/Fuel Valve closed
during ignition.

PRG SWTCH OPEN
DURING PURGE

The Purge Position Limit Switch on the Air/Fuel Valve
opened during purge.

RECIRC PUMP
FAILURE

Internal Recirculation Pump has failed.

REMOTE SETPT
SIGNAL FAULT

The Remote Setpoint signal is not present or is out of range.

RESIDUAL
FLAME

The Flame signal was seen for more than 60 seconds during
standby.

SSOV
SWITCH OPEN

The SSOV switch opened during standby.

SSOV FAULT
DURING PURGE

The SSOV switch opened during purge.

SSOV FAULT
DURING IGN

The SSOV switch closed or failed to open during ignition.

SSOV FAULT
DURING RUN

The SSOV Switch closed for more than 15 seconds during
Run.

SSOV RELAY
FAILURE

A failure has been detected in one of the relays that control
the SSOV.

STEPPER MOTOR
FAILURE

The Stepper Motor failed to move the Air/Fuel Valve to the
desired position.

WARNING EXHAUST
TEMP HIGH (Flashing)

The exhaust gas sensor is measuring high temperature.
Level #1: 180ºF, Flash WARNING
Level #2: 190ºF, Govern fire rate/flash WARNING
Level #3. 200ºF, Shut down unit (requires manual reset)