8.9 WHM PROGRAMMING & START-UP

Prior to programming the required WHM Menu options into the WHM Master and Slaves, all
required hardware installation and network wiring must be completed. In addition, the required
menu entries to be entered must be determined based on the descriptions in the previous
sections.

AERCO recommends that the WHM Master be set up first. By doing so, the Master will “push”
most of the required menu entries to each WHM Slave as each unit is brought on-line. The
following steps assume that the WHM Master and Slaves will be consecutively numbered,
starting at 1 (WHM Master). Proceed as follows starting at the unit which has previously been
determined to be the WHM Master:

WHM Programming & Start-Up Procedure

1. Access the Setup menu and scroll to the Comm Address option. Press the CHANGE key.

2. Enter 1 for the Comm Address of the Master. Press the ENTER key to store the entry.

3. Access the WHM menu and scroll to the WHM Mode option.

4. Press the CHANGE key.

5. Select WHM Master and then press the ENTER key to store the entry. Note that the

Outlet Temperature display on the WHM Master will begin flashing every two seconds.

6. Select the WHM Setpoint option. If you want to change the current setpoint for WHM,

press the CHANGE key.

7. Enter the desired WHM Setpoint temperature and then press ENTER to store the

selection.

8. Scroll to the WHM Nxt On option. If you want to change the value, press the CHANGE

key.

9. Enter the desired value for WHM Nxt On and then press ENTER to store the selection.

10. Scroll to the WHM Nxt Off option. If you want to change the value, press the CHANGE

key.

11. Enter the desired value for Nxt Off and then press ENTER to store the selection.

12. Scroll to the Lead/Lag Hours option. If you want to change the value, press the CHANGE

key.

13. Enter the desired value for the Lead/Lag Hours option and then press ENTER to store

the selection.

14. The WHM menu contains Setback options, which are used to adjust the setpoint

temperature, start time and end time during periods of low DHW demand. These options
are selected in steps 15 through 18, below.

15. To specify the setback temperature, scroll to the Setback Setpoint option. If you want to

change the value, press the CHANGE key.

16. Enter the desired Setback Setpoint temperature and then press ENTER to store the

selection.

17. Next, the Setback Start and Setback End time options must be specified (defaults =

12:00am for both options). To change each option scroll to Setback Start or Setback
End