RECON Water Heaters Installation, Operation & Maintenance Manual

CHAPTER 3 – OPERATION

OMM-0103_0A

AERCO International, Inc.

 100 Oritani Dr.  Blauvelt, NY 10913

Page 49 of 178

GF-147

Phone: 800-526-0288 PRI:

10/28/2014

Menu Item Display

Available Choices or Limits

Default

Minimum

Maximum

13 4-20mA Purge Pct

60%

100%

70%

14 PWM In Adj

-5.0%

5.0%

0.0%

15 Analog In Adj

-5.0% 5.0%

0.0%

16 Flow In Adj

-5.0% 5.0%

0.0%

17 Supply Gas Pressure In Adj

-5.0%

5.0%

0.0%

18 Gas Plate dp In Adj

-5.0%

5.0%

0.0%

19 mA Out Adj

-1.0 mA

1.0 mA

0.0 mA

20 A/F

Sensitivity

1%

5%

2%

21 Power Reset

Automatic or Manual

Automatic

22 Water Temp Reset

Automatic or Manual

Automatic

23 Gas Press Reset

Automatic or Manual

Manual

24 Min Off Time

0 Min

15 Min

0 Min

25 Heatr Tuning Dsp

Enabled or Disabled

Disabled

26 Heatr Bkpt Dsp

Enabled or Disabled

Disabled

27 Stop Level

0%

Start Level

16

28 Start Level

Stop Level

40%

20

29 Skip Range Cntr

10

95

40

30 Skip Range Span

0

3

0

31 Skip

Speed

5

20

5

32 O2

Gain

920

1126

1024

33 O2

Offset

-3.0

+3.0

0

34 O2 Sensor

Enabled or Disabled

Depends on unit type/size

35 Cal Temp Sensors

Enabled or Disabled

36 FFWD Temp Offset

-20

+20

0

37 Exhst

Tmp

Offset

-20

+20

0

38 Outdr Air Offset

-20

+20

0

39 Inlet Air Offset

-20

+20

0

40 Inlet Wtr Offset

-20

+20

0

41 Outlet Wtr Offset

-20

+20

0

42 Spark

Monitor

Enabled or Disabled

Depends on unit type/size

43 Min Spark Amps

0 Amps

2.5 Amps

0.1 Amps

44 Max Spark Amps

0 Amps

2.5 Amps

0.4 Amps