RECON Water Heaters Installation, Operation & Maintenance Manual

CHAPTER 8 – WATER HEATER MANAGEMENT

Page 132 of 178

AERCO International, Inc.

 100 Oritani Dr.  Blauvelt, NY 10913

OMM-0103_0A

PRI: 10/28/2014

Phone: 800-526-0288

GF-147

NOTES:

1.

DO NOT PRESS AUTO-STROKE (RESET) BUTTON. DOING SO MAY ALTER ACTUATOR
CALIBRATION

2.

DEPRESS AND HOLD BRASS CLUTCH BUTTON TO MANUALLY ROTATE VALVE

Figure 8-6: Actuator PC Board Components

-- WARNING! --

Power must be removed from the Actuator prior to attempting to
disengage the clutch. Failure to observe this precaution may
damage the Actuator.


The PC board also contains a brass button which is used to disengage the clutch and permit the
ball valve to be manually rotated. To disengage the clutch, proceed as follows:

Actuator Clutch Disengagement

1. Disconnect the 4-pin connector on the Actuator to ensure that 24 VAC power is not being

supplied

2. Press and hold the brass CLUTCH button shown in Figure 8-6.

3. With the CLUTCH button depressed, the ball valve can be manually rotated from the fully

open (90°) to the fully closed (0°) position.

CLUTCH
(See Note 2, below)

POTENTIOMETER

AUTO-STROKE (RESET) BUTTON
DO NOT PRESS
(See Note 1)

DIP SWITCHES (4)
1–OFF (DOWN)
2–OFF (DOWN)
3–ON (UP)
4–OFF (DOWN)

TERMINALS (5)

Advertising