CHAPTER 5 – SAFETY DEVICE TESTING

Page 68 of 178

AERCO International, Inc.

 100 Oritani Dr.  Blauvelt, NY 10913

OMM-0103_0A

PRI: 10/28/2014

Phone: 800-526-0288

GF-147

5.2 LOW GAS PRESSURE FAULT TEST

Refer to Figure 5-1 and ensure that the leak detection ball valve located at the high gas
pressure switch is closed.

Low Gas Pressure Fault Test

1. Remove the 1/4“ plug from the ball valve at the low gas pressure switch, shown in the lower

portion of Figure 5-1, and then install an NPT to barbed fitting in its place.

2. Install a 0 – 16“ W.C. manometer or a W.C. gauge where the 1/4" plug was removed.

3. Slowly open the ball valve near the low gas pressure switch.

4. Place the unit in Manual Mode and adjust the air/fuel valve position (% open) between 25

and 30%.

5. While the unit is firing, slowly close the external manual gas shut-off valve.

6. Both the RECON 1000 and RECON 500 units should shut down and display a GAS

PRESSURE

fault message at approximately 3.6” W.C. The FAULT indicator should also

start flashing.

7. Fully open the external manual gas shut-off valve and press the CLEAR button on the

Control Box.

8. The fault message should clear and the FAULT indicator should go off. The unit should

restart.

9. Upon test completion, close the ball valve and remove the manometer. Replace the 1/4“

plug removed in step 1.

Figure 5-1: Low and High Gas Pressure Testing

LOW GAS

PRESSURE

SWITCH

HIGH GAS
PRESSURE
SWITCH

MANUAL

SHUTOFF

VALVE

TO AIR/FUEL
VALVE

LEAK
DETECTION
BALL VALVE

1/4" NPT PLUG
(Install manometer here for
HIGH GAS PRESSURE TEST)

GAS INLET

SSOV

1/4" NPT PLUG

(Install manometer here for

LOW GAS PRESSURE TEST)

LEAK

DETECTION

BALL VALVE