AERCO RECON 1000 User Manual

Page 44

Advertising
background image

RECON Water Heaters Installation, Operation & Maintenance Manual

CHAPTER 3 – OPERATION

Page 44 of 178

AERCO International, Inc.

 100 Oritani Dr.  Blauvelt, NY 10913

OMM-0103_0A

PRI: 10/28/2014

Phone: 800-526-0288

GF-147

3.4 OPERATING MENU

The Operating Menu displays a number of key operating parameters for the unit, as listed in
Table 3-2. This menu is “Read-Only” and does not allow personnel to change or adjust any
displayed items. It can therefore be viewed at any time without entering a password. Pressing
the ▲ arrow key to display the menu items in the order listed (Top-Down). Pressing the ▼
arrow key will display the menu items in reverse order (Bottom-Up).

A full description of each item appears in Table A-1 of Appendix A – Recon Menu Item
Descriptions.

Table 3-2: Operating Menu

Menu Item Display

Available Choices or Limits Appears only if enabled

in the following menu:

Minimum

Maximum

1 Active

Setpoint

40°F

190°F

2 Inlet

Temp

30°F

240°F

Calibration

Menu

3 Air

Temp

-70°F

245°F

4

* Outdoor Temp

-70°F

130°F

Configuration Menu

5

Valve Position In

0%

100%

6 Exhaust

Temp

40°F

560°F

7

Valve Position Out

0%

100%

Calibration Menu

8 FFWD

Temp

30°F

240°F

Calibration

Menu

9 Flame

Strength

0%

100%

10 Oxygen

Level

-32%

32%

11 Ignition

Time

0.00

10.00

12

SSOV Time to OPN

0.00

10.00

13 Run

Cycles

0

999,999,999

14 Run

Hours

0

999,999,999

15

Fault Log

0

19

* NOTE

The Outdoor Temp display item will not be displayed unless the
Outdoor Sensor function has been enabled in the Configuration
Menu (Table 3-4).