RECON Water Heaters Installation, Operation & Maintenance Manual

CHAPTER 5 – SAFETY DEVICE TESTING

Page 76 of 178

AERCO International, Inc.

 100 Oritani Dr.  Blauvelt, NY 10913

OMM-0103_0A

PRI: 10/28/2014

Phone: 800-526-0288

GF-147

Figure 5-6: SSOV Actuator Cover Location


5.10 PURGE SWITCH OPEN DURING PURGE

The Purge Switch (and Ignition Switch) is located on the Air/Fuel Valve. To check the switch,
proceed as follows:

Purge Switch Open During Purge

1. Set the unit’s ON/OFF switch to the OFF position. Place the unit in manual mode and set the

valve position between 25% and 30%.

2. Remove the Air/Fuel Valve cover by rotating the cover counterclockwise to unlock it (see

Figure 5-7).

3. Remove one of the two wires (#171 or #172) from the Purge Switch (Figure 5-8).

4. Initiate a unit start sequence.

5. The unit should begin its start sequence, then shut down and display PRG SWITCH OPEN

DURING PURGE.

6. Replace the wire on the Purge Switch and depress the CLEAR button. The unit should

restart.


SSOV ACTUATOR
COVER

ACTUATOR

COVER SCREW

SSOV