CHAPTER 6: MAINTENANCE

6.1 MAINTENANCE SCHEDULE

The RECON Water Heater requires regular routine maintenance to ensure continued reliable
operation throughout the service life of the unit. For optimum operation, AERCO recommends
that the following routine maintenance procedures be performed in the time periods specified in
Table 6-1.

Appendix I contains a list of the recommended spare parts for maintenance of RECON units.

--WARNING! -

To avoid personal injury, prior to servicing ensure that the following
guidelines are strictly observed:
 Disconnect the AC supply by turning off the service switch and

AC supply circuit breaker.

 Shut off the gas supply at the manual shut-off valve provided with

the Unit

 Allow the Unit to cool to a safe water temperature to prevent

burning or scalding

Table 6-1: Maintenance Schedule

Section

Item

6 Mos.

12 Mos.

24 Mos.

Labor

Time

6.2

Igniter-Injector

(58023)

* Inspect

* Inspect

Replace

15 min.

6.3

Flame Detector

(kit # 24356-2)

* Inspect

* Inspect

Replace

15 min.

6.4

Combustion

Calibration

* Check

Check

1 hr.

6.5

Testing of

Safety Devices

Test

20

min.

6.6

Fireside

Inspection

Inspect &

Clean

2 hrs.

6.7

Waterside

Inspection

* Inspect

Inspect

1 hr.

6.8

Heat Exchanger

Cleaning

Inspect & Clean

(as required)

2 hrs.

6.9

Condensate

Drain Trap

Inspect

Inspect & Clean

30 min.

6.10

Air Filter

(59139)

* Inspect

* Inspect

Replace

5 min.

*

Replace as necessary.