CHAPTER 6 – MAINTENANCE

Page 90 of 178

AERCO International, Inc.

 100 Oritani Dr.  Blauvelt, NY 10913

OMM-0103_0A

PRI: 10/28/2014

Phone: 800-526-0288

GF-147

6.8.1 Pumping System Set-Up

A sample pumping set-up diagram is shown in Figure 6-9 A and 6-9 B. As this diagram shows,
heat exchanger cleaning is accomplished by pumping the HydroSkrub solution from a large
circulation bucket to the heat exchanger drain valve, through the heat exchanger and then out
through the output connection of the heater. Set up the pumping system as follows:

Pumping System Set-Up Instructions

1. Turn off the water heater and close the inlet and outlet isolation valves.

2. Open the drain valve (see Figure 6-9 B) and drain at least half of the heat exchanger water-

side volume. When full, RECON models hold approximately the following gallons of water:

 RECON500: 27 gallons
 RECON1000: 25 gallons

NOTE: The volume of water drained must equal the volume of HydroSkrub added.

3. Route the test hose bib (see section 2.6, above,) ball valve and hose connection from the hot

water outlet piping to the top of a suitably sized circulation bucket (see Figure 6-9 A).

Figure 6-9 A: Sample Heat Exchanger Cleaning Set-Up

4. Close the hot water outlet and cold water inlet valves.

5. Connect a pump from the circulation bucket to the drain valve (see Figure 6-9 B).

TEST HOSE BIB

CONNECTION

UNION

BACK-FLOW

PREVENTOR

CLOSE COLD

WATER INLET

VALVE

COLD

WATER

IN

PUMP

CIRCULATION

BUCKET

HOT WATER OUTLET
CONNECTION

CONNECT TO DRAIN

VALVE ON RIGHT SIDE,

SEE FIGURE 6-9 B

LEFT SIDE VIEW

HOT WATER

OUTLET VALVE