RECON Water Heaters Installation, Operation & Maintenance Manual

CHAPTER 6 – MAINTENANCE

OMM-0103_0A

AERCO International, Inc.

 100 Oritani Dr.  Blauvelt, NY 10913

Page 97 of 178

GF-147

Phone: 800-526-0288 PRI:

10/28/2014

LWCO Capacitor Integrity Test – Continued

5. Confirm that the ohmmeter does NOT read a short.

NOTE

If the ohmmeter reads a short, the capacitor assembly needs to be replaced.
Refer to document TID-0094, provided with the 24-month maintenance kit,
for LWCO replacement instructions.

6. Remove both ohmmeter probes and reconnect the Shell Harness connector to the P5

connector on the rear of the C-More controller.

6.11.2 Low Water Cutoff (LWCO) - Standard C-More Test

Perform the standard Low Water Cutoff test using the C-More controls as described below.

Standard Low Water Cutoff C-More Test

1. Turn on the AC power to the unit.

2. Press the TEST switch on the C-More controller and confirm that the blinking "Low Water

Level" message appears on the C-More display within 4 seconds.

3. Press the RESET key, followed by the Clear button, and confirm that the "Low Water

Level" message is cleared.