AERCO RECON 1000 User Manual
Page 36
 
RECON Water Heaters Installation, Operation & Maintenance Manual
CHAPTER 2 – INSTALLATION
Page 36 of 178
AERCO International, Inc.
 100 Oritani Dr.  Blauvelt, NY 10913
OMM-0103_0A
PRI: 10/28/2014
Phone: 800-526-0288
GF-147
2.12.14 AUX RELAY Terminals
Each unit is equipped with a single pole double throw (SPDT) auxiliary relay that is energized 
when there is a demand for heat and de-energized after the demand for heat is satisfied. The 
relay is provided for the control of auxiliary equipment, such as pumps and louvers, or can be 
used as a unit status indictor (firing or not firing). Its contacts are rated for 120 VAC @ 5 amps. 
Refer to Figure 2-14 to locate the AUX RELAY terminals (N.C., COM, & N.O.) for wiring 
connections. 
2.13 FLUE GAS VENT INSTALLATION
The Innovation and RECON Venting and Combustion Air Guide, GF-5050 must be consulted 
before any flue or combustion air venting is designed or installed – please contact the factory to 
request a copy of this guide. Suitable, UL approved, positive pressure, watertight vent materials 
MUST be used for safety and UL certification. Because the unit is capable of discharging low 
temperature exhaust gases, the flue must be pitched back towards the unit a minimum of 1/4" 
per foot to avoid any condensate pooling and to allow for proper drainage. 
While there is a positive flue pressure during operation, the combined pressure drop of vent and 
combustion air systems must not exceed 140 equivalent feet or 0.81” W.C with 6” piping. 
Fittings as well as pipe lengths must be calculated as part of the equivalent length. For a natural 
draft installation the draft must not exceed - 0.10” W.C. These factors must be planned into the 
vent installation. If the maximum allowable equivalent lengths of piping are exceeded, the unit 
will not operate properly or reliably. 
For Massachusetts installations, the following companies provide vent systems which conform 
to all applicable requirements for installations within the Commonwealth of Massachusetts. 
Contact information is as follows: 
Selkirk Corporation - Heatfab Division 
130 Industrial Blvd. 
Turners Falls, MA 01376 
Phone: 1-800-772-0739 
www.heat-fab.com
Watertown Supply 
33Grove St. 
Watertown, MA 02472 
Phone: (617) 924-2840 
http://www.watertownsupply.com/
M. A. Peacard 
1250 Massachusetts Ave. 
Boston MA 02125-1689 
Phone: (617) 288-0629 
www.mapeacard.com
Glover Sheet Metal, Inc. 
44 Riverdale Ave. 
Newton, MA 02485 
Phone: (617) 527-8178 
www.gloversheetmetal.com
2.14 COMBUSTION AIR
The Innovation and RECON Venting and Combustion Air Guide, GF-5050, MUST be consulted 
before any flue or inlet air venting is designed or installed. Air supply is a direct requirement of 
ANSI 223.1, NFPA-54, CSA B149.1 and local codes. These codes should be consulted before a 
permanent design is determined. 
The combustion air must be free of chlorine, halogenated hydrocarbons or other chemicals that 
can become hazardous when used in gas-fired equipment. Common sources of these 
compounds are swimming pools, degreasing compounds, plastic processing, and refrigerants. 
Whenever the environment contains these types of chemicals, combustion air MUST be 
supplied from a clean area outdoors for the protection and longevity of the equipment and 
warranty validation.