RECON Water Heaters Installation, Operation & Maintenance Manual

CHAPTER 4 – INITIAL START-UP

OMM-0103_0A

AERCO International, Inc.

 100 Oritani Dr.  Blauvelt, NY 10913

Page 61 of 178

GF-147

Phone: 800-526-0288 PRI:

10/28/2014

NATURAL GAS Combustion Calibration – Continued

Figure 4-4: Gas Pressure Adjustment Screw Location

13. Replace the brass cap on the SSOV gas pressure adjustment if it was previously removed.

14. With the valve position at 100%, insert the combustion analyzer probe into the flue probe

opening and allow enough time for the combustion analyzer reading to stabilize.

15. Compare the oxygen (O

2

)

level, carbon monoxide (CO), nitrogen oxide (NOx) and flame

strength readings with the range

shown in step 19, below. You may need to adjust O

2

% above

this range to meet ultra-low NOx requirements or to avoid combustion tone issues.

16. Press the MENU key on the front panel of the C-More until Combustion Cal Menu appears

on the display.

17. Press the ▲ arrow key until SET Valve Position reads 100%. Press the ENTER key.

18. Press the CHANGE key and observe that CAL Voltage 100% is flashing.

19. The oxygen level at the 100% valve position should be as shown below. Also, ensure that the

nitrogen oxide (NOx), carbon monoxide (CO) and flame strength readings match the following
values:

Combustion Calibration Readings

at 100% Valve Position

Valve

Position

Oxygen (O

2

)

%

Nitrogen Oxide

(NOx)

Carbon Monoxide

(CO)

Flame µA

100%

6.0% ± 0.25%

<20 ppm

<100 ppm

> 6 µA

20. If the oxygen level is not within the specified range, adjust the level using the ▲ and ▼ arrow

keys. This will adjust the output voltage to the blower motor as indicated on the display.
Pressing the ▲ arrow key increases the oxygen level and pressing the down ▼ arrow key
decreases the oxygen level.

21. Once the oxygen level is within the specified range at 100%, press the ENTER key to store the

selected blower output voltage for the 100% valve position. Record all readings on the
Combustion Calibration Sheets provided.

22. Repeat steps 16 through 21 for the following valve positions (see NOTE below):

 RECON 1000: 80%, 60%, 50%, 40%, 30%, 20%

RECON 500: 80%, 60%, 40%, 30%, 24%, 20%, 16%

BRASS HEX
HEAD CAP

(Remove to access gas
pressure adjustment screw)