CHAPTER 5 – SAFETY DEVICE TESTING

Page 74 of 178

AERCO International, Inc.

 100 Oritani Dr.  Blauvelt, NY 10913

OMM-0103_0A

PRI: 10/28/2014

Phone: 800-526-0288

GF-147

Air Flow Fault Tests – Continued

6. Once the unit has proved flame, turn off the blower by going to the Configuration Menu,

Analog Output menu item and select OFF.

7. The Blower Proof Switch will open and the blower should stop. The unit should shut down

and display AIRFLOW FAULT DURING RUN.

8. Go to the Configuration Menu, Analog Output item and select VALVE POSITION 0-10v.

9. Press the CLEAR button. The unit should restart.

10. Next, check the operation of the Blocked Inlet Switch located on the inlet side of the Air/Fuel

Valve (Figure 5-4).

11. Ensure that the sheet metal panels are securely installed on the water heater and the unit is

running.

12. At the rear of the unit, partially block the air inlet (Figure 5-5) with a plywood sheet or metal

plate.

13. The unit should shut down and again display AIRFLOW FAULT DURING RUN.

14. Unblock the air inlet and press the CLEAR button. The unit should restart.

Figure 5-4: Blower Proof & Blocked Inlet Switch Locations

(A/F Valve Clear Cover Removed)

AIR/FUEL
VALVE

BLOWER

BLOCKED

INLET

SWITCH

BLOWER

PROOF

SWITCH

AIR FILTER

A/F VALVE
STEPPER
MOTOR