RECON Water Heaters Installation, Operation & Maintenance Manual

CHAPTER 3 – OPERATION

OMM-0103_0A

AERCO International, Inc.

 100 Oritani Dr.  Blauvelt, NY 10913

Page 47 of 178

GF-147

Phone: 800-526-0288 PRI:

10/28/2014

3.7 TUNING MENU

The Tuning Menu items in Table 3-5 are Factory set for each individual unit. Do not change
these menu entries unless specifically requested to do so by Factory-Trained personnel.

A full description of each item appears in Table A-4 of Appendix A – Recon Menu Item
Descriptions.

Table 3-5: Tuning Menu

Menu Item Display

Available Choices or Limits

Default

Minimum

Maximum

1

Prop Band

1°F

200°F

30°F

2

Integral Gain

0.00

10.00

3.00

3

Derivative Time

0.00 min

2.00 min

0.20 min

4

Min Load Adj

-50°F

+50°F

0°F

5

Max Load Adj

-50°F

+50°F

0°F

6

FFWD Temp

30°F

245°F

Read Only Value

7

Outlet Feedback

Yes (On) or No (Off)

Yes (On)

8 Feedback

Gain

0.01

1.00

0.10

Breakpoints – shown only if the Calibration Menu item (see section 3-8) Heatr Bkpt Dsp =
Enabled. The Breakpoint values correspond to a 130°F default setpoint

9

Breakpt at 100%

30°F

240°F

85°F

10

Breakpt at 90%

30°F

240°F

86°F

11

Breakpt at 80%

30°F

240°F

87°F

12

Breakpt at 70%

30°F

240°F

88°F

13

Breakpt at 60%

30°F

240°F

89°F

14

Breakpt at 50%

30°F

240°F

90°F

15

Breakpt at 40%

30°F

240°F

94°F

16

Breakpt at 30%

30°F

240°F

103°F

17

Breakpt at 20%

30°F

240°F

118°F

18

Breakpt at 10%

30°F

240°F

134°F

19

Breakpt at 0%

30°F

240°F

136°F

WHM Items – the remaining items below appear only if WHM is enabled:

20 FDback Start Pos

0% 100%

30%

21 Fdback End Pos

0% 100%

60%

22 Max

Feedback

0% 100%

30%

23 Fdback

Value

0%

100%

Read Only Value