Table A-5: Calibration Menu Item Descriptions

Table A-5: CALIBRATION MENU ITEM DESCRIPTIONS

See section 3-8 for a range of choices and the default values.

MENU LEVEL & OPTION

DESCRIPTION

1

Stepper Fbk

Allows the Air/Fuel Valve stepper motor feedback current to be
calibrated at the 0% (fully closed) and 100% (fully open) positions.
Verification can also be accomplished at the 50% position.

2

Purge Timer

Allows adjustment of the pre-ignition purge time.

3

Post Purge Timer

Allows adjustment of the purge time when a unit shuts down.

4

IGN Position

Allows adjustment of the valve position (Fire Rate) during the ignition
sequence.

5

FFWD Temp Disply

Enabled or Disabled.

6

Outlet Tmp Dsply

Enabled or Disabled.

7

Inlet Tmp Dsply

Enabled or Disabled.

8

Valv Pos Out Dsp

Enabled or Disabled.

9

Exhaust Tmp Dsp

Enabled or Disabled.

10

VP Up Rate

Allows adjustment of the Valve Position (Fire Rate) increase rate
when raising the Valve Position. VP Up Rate is defined as Seconds
per Step.

11

VP Down Rate

Allows adjustment of the Valve Position (Fire Rate) decrease rate
when lowering the Valve Position. VP Down Rate is defined as
Seconds per Step.

12

Purge Blwr Offst

Allows adjustment of the blower speed (Blower Output Voltage)
during the Purge cycle.

13

4-20mA Purge Pct

Allows adjustment of the blower speed (Blower Output Voltage)
during the Purge cycle when using an Emerson VFD Drive to control
the Blower Motor.

14

PWM In Adj

Allows the Pulse Width Modulation (PWM) duty cycle to be adjusted
from -5.0% to +5.0% in 0.1% increments.

15

Analog In Adj

Allows adjustment of the analog input from -5.0% to +5.0%.

16

Flow In Adj

Allows adjustment of the water Flow Rate Input from
-5.0% to +5.0%.

17

Supply Gas Pressure
In Adj

Allows adjustment of the Supply Gas Pressure level from
-5.0% to +5.0% in 0.1 % increments.

18

Gas Plate dp In Adj

Allows adjustment of the Gas Plate dp level from -5.0% to +5.0% in
0.1% increments.

19

mA Out Adj

Allows adjustment of the milliamp output from -5.0 mA to +5.0 mA.

20

A/F Sensitivity

Allows adjustment of the Air/Fuel (A/F) Valve stepper motor sensitivity
to be adjusted from 1% to 5% in 1% increments.

21

Power Reset

Allows the Power Reset Option to be set to Auto or Manual.