3 vents, 5 top output, 6 floor output – EVCO EVF328J9 User Manual

Page 21

Advertising
background image

EVCO S.p.A.

EVF 300 series | Installer manual ver. 1.1 | Code 144F300E114

Page 21 of 62

7.3

Vents

7.3.1

Preliminary notes

Pressing and releasing the "VENT" key will cause the activation

of the vent (at maximum or the time established with

parameter c7 or until the key is pressed and released again).

The vent is also activated for the time established with

parameter c6 with the advance defined with parameter c5 on

conclusion of the cooking timer count.

7.3.2

Manual activation of the vent

Operate as follows to activate the vent in manual mode:

1.

Ensure that the device is switched on and that no

other procedure is in progress.

2.

Press and release the "VENT" key: the vent will be

switched on (at maximum for the time established

with parameter c7 or until the key is pressed and

released again).

7.3.3

Extraction hood (only if parameter u1 is set

at 0)

If the device is on and the parameter i0 is set at 1 or 2, the

activation of the door micro switch will cause the extraction

hood to switch-on (until the input is deactivated).

7.4

Multi-function output (only if

parameter u1 is set at 1)

7.4.1

Preliminary notes

Pressing the "VENT" key for 1 s will cause the multi-function

output to switch on (until the key is pressed again for 1 s or

until the device is switched off).

7.4.2

Switching on the multi-function output

Operate as follows to switch on the multi-function output:

1.

Ensure that the device is switched on and that no

other procedure is in progress.

2.

Hold the “VENT” key down for 1 s: the “M:F” LED

will switch on and the multi-function output will be

switched-on (until the key is held down again for 1

s or until the device is switched off).

7.4.3

Technical compartment fan (only if

parameter u11 is set at 0)

The activity of the technical compartment fan depends mainly

on the state of the device, as follows:

-

if the device is on, the fan will be on

-

if the device is switched off, the fan will be

switched off.

The technical compartment fan is off with the delay

established with parameter u12 from device switch-off

7.4.4

Output switch-on/off (only if parameter u11

is set at 1)

The activity of the output switch-on/off depends mainly on the

state of the device, as follows:

-

if the device is on, the output will be on

-

if the device is off, the output will be off.

7.5

Top output

If the device is on, top output activity depends mainly on the

CFG parameter, as follows:

-

if the CFG parameter is set at 0, the distribution of

power will be active until the temperature of the

chamber has reached the work set-point and will

be reactivated when the temperature drops below

that established with parameter r0 (i.e. “work set-

point - r0”). When the distribution of power is

active, the top output is on in cyclic mode, as

much as possible when the floor output is off (the

time established with parameter c1 establishes the

cycle time for switch-on of the output and the

power distributed at the top establishes the

duration of output switch-on, intended as a

percentage of the time established with parameter

c1)

-

if the CFG parameter is set at 1, the output will be

switched-on until the temperature of the top has

reached the top set-point and will be switched

back on when the temperature falls below that

established with parameter r0 (i.e. top set-point -

r0").

7.6

Floor output

If the device is on, floor output activity depends mainly on the

CFG parameter, as follows:

-

if the CFG parameter is set at 0, the distribution of

power will be active until the temperature of the

chamber has reached the work set-point and will

be reactivated when the temperature drops below

that established with parameter r0 (i.e. “work set-

point - r0”). When the distribution of power is

active, the floor output is on in cyclic mode, as

much as possible when the floor output is off (the

time established with parameter c1 establishes the

cycle time for switch-on of the output and the

power distributed at the floor establishes the

duration of output switch-on, intended as a

percentage of the time established with parameter

c1)

-

if the CFG parameter is set at 1, the output will be

switched-on until the temperature of the floor has

reached the floor set-point and will be switched

back on when the temperature falls below that

established with parameter r6 (i.e. top set-point -

r6").