16

ALARMS

16.1

Alarms

The following table illustrates the meaning of the device alarm codes.

CODE

MEANING

AH1

if the parameter CFG is set at 0, temperature

solutions:

-

check the chamber temperature; see parameters A1 and A3

main consequences:

- no

consequence

if the parameter CFG is set at 1, top temperature alarm

solutions:

-

check the top temperature; see parameters A1 and A3

main consequences:

- no

consequence

AH2

floor temperature alarm

solutions:

-

check the top temperature; see parameters A1 and A3

main consequences:

- no

consequence

Ht

Use temperature alarm.

solutions:

-

check the use temperature of the control module; see parameter P7

-

when the cause of the alarm disappears, press and release a key

main consequences:

-

the device will be switched off

-

the technical compartment fan will be on (only if parameter u11 is set at 0) and the remaining

outputs will be off

dr

door micro switch input alarm

solutions:

-

check the causes of the activation of the input; see parameters i0 and i1,

main consequences:

-

the effect established with parameter i0

AL1

circuit breaker protection input alarm

solutions:

-

check the causes of the activation of the input; see parameter i11,

main consequences:

-

if the alarm occurs when the device is on, a cooking cycle cannot be started

-

if the alarm occurs during a cooking cycle, the cycle will be interrupted

-

steam injection will be disables, the steam generator, to top output and the floor output will be

switched off