EVCO S.p.A.

EVF 300 series | Installer manual ver. 1.1 | Code 144F300E114

Page 38 of 62

CFG

0

1

- - -

0

1

type of operation

0 = with one analogue input (chamber probe, i.e.

with management of the power supplied at the

top and at the floor independently from each

other.)

1 = with two analogue inputs (top and floor probe,

i.e. with management of the temperature of the

top and at the floor independently from each

other.)

PARAM.

MIN.

MAX.

U.M.

INP. 1

INP. 2

ANALOGUE INPUTS

CA1 -25/-50 25/50 °C/°F

(1)

0

0

if CFG = 0, chamber probe offset

if CFG = 1, top probe offset

CA2

-25/-50

25/50

°C/°F (1)

not dis.

0

floor probe offset

CA3

-25/-50

25/50

°C/°F (1)

0

0

steam probe offset

P0

0

1

- - -

0

0

probe type

0 = thermocouple

J

1 = thermocouple

K

P2

0

1

- - -

0

0

temperature unit of measurement (2)

0 =

°C

1 =

°F

P4

0

2

- - -

2

2

steam injection activation consent mode

0 = MANUAL - steam injection will be allowed if the

steam generator has been switched on

1 = REMOTE - steam injection will be allowed if the

steam generator has been switched on and if the

multi-function input has been activated (until

the input is deactivated; only if i5 = 1)

2 = THERMOSTAT - steam injection will be allowed if

the steam temperature adjustment has been

activated and the steam temperature is above

the SPS (until the temperature drops below the

t4 value)

P5

0

1

- - -

0

0

information shown in the top part of the "UPPER" display

when the device is on and when a cooking cycle is in

progress

0 = if CFG = 0, temperature of the chamber

if CFG = 1, top temperature

1 = if CFG = 0, work set-point

if CFG = 1, top set-point