EVCO S.p.A.

EVF 300 series | Installer manual ver. 1.1 | Code 144F300E114

Page 51 of 62

17

ERRORS

17.1

Errors

The following table illustrates the meaning of the device error codes.

CODE

MEANING

Pr1

if the parameter CFG is set at 0, chamber probe error

solutions:

-

check that the probe is the thermocouple J or thermocouple K type

-

check the device-probe connection

-

check the temperature of the chamber

main consequences:

-

if the alarm occurs when the device is on, a cooking cycle cannot be started

-

if the alarm occurs during a cooking cycle, the cycle will be interrupted

-

the top output and the floor output will be switched off

if the parameter CFG is set at 1, top probe error

solutions:

-

the same as the preceding case but with respect to the top probe

main consequences:

-

the floor probe will function as top probe and as floor probe

Pr2

floor probe error

solutions:

-

the same as the preceding case but with respect to the floor probe

main consequences:

-

the top probe will function as top probe and as floor probe

Pr3

steam probe error

solutions:

-

the same as the preceding case but with respect to the steam probe

main consequences:

-

if parameter P4 is set at 2, steam injection will be disabled and the steam generator will be

switched off

E0C

cold joint error

solutions:

-

cut the device power supply off

main consequences:

-

if the error occurs when the device is on, a cooking cycle cannot be started

-

if the error occurs during a cooking cycle, the cycle will be interrupted

-

all outputs will be switched off

rtc

clock error

solutions:

-

set the day of the week and the time

main consequences:

-

the “weekly programmed switch-on” function will not be available