EVF 300 series | Installer manual ver. 1.1 | Code 144F300E114

Page 42 of 62

PARAM.

MIN.

MAX.

U.M.

INP. 1

INP. 2

TEMPERATURE ALARMS

A1 0 999

°C/°F

(1)

0 0

if CFG = 0, temperature of the chamber above which the

temperature alarm is activated (code “AH1”); see also

A3 (8)

if CFG = 1, temperature of the top above which the

temperature alarm is activated (code “AH1”); see also

A3 (8)

A2 0 240 min 0 0

if CFG = 0, temperature alarm display (code “AH1”)

if CFG = 1, top temperature alarm delay (code “AH1”)

A3

0

2

- - -

0

0

if CFG = 0, temperature alarm type (code “AH1”)

if CFG = 1, top temperature alarm type (code “AH1”)

0 = no alarm

1 = absolute (i.e. A1)

2 = if CFG = 0, relative to the work set-point (i.e.

“work set-point + A1”)

if CFG = 1, relative to the top set-point (i.e. “top

set-point + A1”)

A4 0 999

°C/°F

(1)

not

dis.

0

temperature of the floor above which the floor

temperature alarm is activated (code “AH2”); see also

A6 (8)

A5

0

240

min

not dis.

0

floor temperature alarm delay (code “AH2”)

A6

0

2

- - -

not dis.

0

type of floor temperature alarm (code “AH2”)

0 = no alarm

1 = absolute (i.e. A4)

2 = relative to the floor set-point (i.e. “floor set-

point + A4”)

PARAM.

MIN.

MAX.

U.M.

INP. 1

INP. 2

DIGITAL INPUTS