EVCO EVF328J9 User Manual

Page 43

Advertising
background image

EVCO S.p.A.

EVF 300 series | Installer manual ver. 1.1 | Code 144F300E114

Page 43 of 62

i0

0

2

- - -

2

2

effect caused by the activation of the door micro switch

input

0 = no

effect

1 = EXTRACTION HOOD SWITCH-ON - the extraction

hood will be switched on (only if

u1 = 0, until the input is deactivated)

2 = SWITCH-ON OF THE EXTRACTION HOOD,

SWITCH-OFF OF THE TOP OUTPUT AND FLOOR

OUTPUT AND DISABLING OF STEAM INJECTION

- the extraction hood will be switched on (only if

u1 = 0); the top output and the floor output will

be switched off and the steam injection will be

disabled (until the input will be deactivated)

i1

0

1

- - -

0

0

type of door micro switch input contact

0 = normally open (input active with closed contact)

1 = normally closed (input active with open contact)

i5

0

1

- - -

1

1

effect caused by the activation of the multifunction input

0 = no

effect

1 = CONSENT FOR STEAM INJECTION - steam

injection will be allowed (until the input s

deactivated, only if

P4 = 1)

1 = DEVICE SWITCH-OFF - the device will be

switched off (while the input is deactivated)

i6

0

1

- - -

0

0

type of multifunction input contact

0 = normally open (input active with closed contact)

1 = normally closed (input active with open contact)

i11

0

1

- - -

0

0

type of circuit breaker protection input contact

0 = normally open (input active with closed contact)

1 = normally closed (input active with open contact)

i12 0 120 s

10 10

input circuit breaker protection alarm signal delay

(“AL1” code)