Calibration

95

6. Apply the correct span resistance to channel 0, detail resistance

value, see table 5-1.

7. Send

Span Calibration $(Addr)0” to analog input module five

times.

Repeat procedure 3 to procedure 7 two times.

Calibration Procedure for ND-6018 Firmware Rev B1.10

1. Disable all the channel and open detect function.
2. Select the correct input range, different input range have different

apply calibration voltage.

3. Apply the correct offset voltage to channel 0, detail voltage

value, see table 5-1.

4. Send

Offset Calibration $(Addr)1” to analog input module five

times.

5.

Apply the correct span voltage to channel 0, detail voltage value,
see table 5-1.

6. Send

Span Calibration $(Addr)0” to analog input module five

times.

Repeat procedure 3 to procedure 6 two times.

Calibration Procedure for ND-6018 Firmware Rev E1.00 and

e1.00

1. Power off the module.
2. Connect the default pin to GND.(Because the calibration

procedures must be run under default mode).

3. Power on the module and use utility searching the module.
4. There must a “*” before the address ID.
5. Disable open detect function by sending command “$00O0”.
6. Only enable Ch0.
7. Select the correct input range. Different input range has to apply

different calibration voltage.

8. Apply the correct offset voltage to channel 0, detail voltage value,

see table 5-1.

9. Send

Offset Calibration $(Addr)1” to analog input module five

times.(Actually, the address now is “00”, so the command is
“$001”).

10. Apply the correct span voltage to channel 0, detail voltage value,

see table 5-1.