19 read cjc status – ADLINK ND-6018 User Manual
Page 64
Advertising
![background image](/manuals/733487/64/background.png)
56
• Command Set
3.19 Read CJC Status
@Description
Read the CJC (Cold Junction Compensation) sensors data.
@Syntax
$(Addr)3<CR>
$
Command leading code.
(Addr)
Address ID
3
Read CJC status.
@Response
>(Data)<CR>
or
?(Addr)<CR
>
>
Command is invalid.
(Data)
CJC sensor’s data.
Data format is engineering units. (an + or - sign with
five decimal digits and a decimal fixed point. The
resolution is 0.1
°C
?
Command is invalid.
(Addr)
Address ID.
@Example
User command:
$063<CR>
Response:
>+0037.9<CR>
This command is to read analog input module CJC status at address
06H, return data is 37.9
°C.
(6011/D, 6018)