19 read cjc status – ADLINK ND-6018 User Manual

Page 64

Advertising
background image

56

Command Set

3.19 Read CJC Status

@Description

Read the CJC (Cold Junction Compensation) sensors data.

@Syntax

$(Addr)3<CR>

$

Command leading code.

(Addr)

Address ID

3

Read CJC status.

@Response

>(Data)<CR>
or
?(Addr)<CR
>

>

Command is invalid.

(Data)

CJC sensor’s data.
Data format is engineering units. (an + or - sign with
five decimal digits and a decimal fixed point. The
resolution is 0.1

°C

?

Command is invalid.

(Addr)

Address ID.

@Example

User command:

$063<CR>

Response:

>+0037.9<CR>


This command is to read analog input module CJC status at address
06H, return data is 37.9

°C.

(6011/D, 6018)