22 read source high/low values for linear mapping – ADLINK ND-6018 User Manual

Page 67

Advertising
background image

Command Set

59

3.22 Read Source High/Low Values for Linear

Mapping

@Description

Read the high/low limit values from input for linear mapping.

@Syntax

$(Addr)3<CR>

$

Command leading code.

(Addr)

Address ID

3

Read the high/low limit values from input for linear
mapping .

@Response

!(Addr)(Data_L)(Data_H)<CR>
or
?(Addr)<CR>

!

Command is invalid.

(Addr)

Address ID.

(Data_L)

Low limit value for linear mapping.
Data format is with an + or - sign with five decimal
digits and a decimal fixed point.

(Data_H)

High limit value for linear mapping.
Data format is with an + or - sign with five decimal
digits and a decimal fixed point.

?

Command is invalid.

@Example

User command:

$023<CR>

Response:

!02+04.000+20.000<CR>

The module is configured for +20~-20mA input current range. The linear
mapping function should already have been executed. This command is
to read the high/low values for linear mapping. The high limit value is
+20mA and low limit value is +4mA. The address of this module is 06H.

(6014D)