38 read high alarm limit – ADLINK ND-6018 User Manual

Page 84

Advertising
background image

76

Command Set

3.38 Read High Alarm Limit

@Description

Read the high alarm limit at specified analog input module.

@Syntax

@(Addr)RH<CR>

@

Command leading code.

(Addr)

Address ID

RH

Read high alarm limit.

@Response

!(Addr)(Data)<CR>

!

Command is valid.

(Addr)

Address ID.

(Data)

High alarm limit value.
Data format is engineering units. (an + or - sign with
five decimal digits and a decimal fixed point.

@Example

User command:

@06RH<CR>

Response:

!06+01.500<CR>


Read the high alarm limit value at address 06H, its value is 1.500 Volts,
presume this module is configured to accept

±2.5 Volts input.

(6011/D, 6012/D, 6014D)