23 read target high/low values for linear mapping – ADLINK ND-6018 User Manual

Page 68

Advertising
background image

60

Command Set

3.23 Read Target High/Low Values for Linear

Mapping

@Description

Read the mapped high/low limit values from input for linear mapping.

@Syntax

$(Addr)5<CR>

$

Command leading code.

(Addr)

Address ID

5

Read the mapped high/low limit values from input for
linear mapping .

@Response

!(Addr)(Data_L)(Data_H)<CR>
or
?(Addr)<CR>

!

Command is invalid.

(Addr)

Address ID.

(Data_L)

Mapped low limit value for linear mapping.
Data format is with an + or - sign with five decimal
digits and a decimal fixed point.

(Data_H)

Mapped high limit value for linear mapping.
Data format is with an + or - sign with five decimal
digits and a decimal fixed point.

?

Command is invalid.

@Example

User command:

$055<CR>

Response:

!05-20.000+20.000<CR>


The module is configured for +20~-20mA input current range. The linear
mapping function had been executed. This command is to read the
mapped high/low values for linear mapping. The mapped high limit
value is +20mA and mapped low limit value is -20mA. The address of
this module is 05H.

(6014D)