39 read low alarm limit – ADLINK ND-6018 User Manual

Page 85

Advertising
background image

Command Set

77

3.39 Read Low Alarm Limit

@Description

Read the low alarm limit at specified analog input module.

@Syntax

@(Addr)RL<CR>

@

Command leading code.

(Addr)

Address ID, range (00 - FF).

RL

Read low alarm limit.

@Response

!(Addr)(Data)<CR>

!

Command is valid.

(Addr)

Address ID.

(Data)

Alarm low limit value.
Data format is engineering units. (an + or - sign with
five decimal digits and a decimal fixed point.

@Example

User command:

@06RL<CR>

Response:

!06-0.3850<CR>


Read the low alarm limit value at address 06H, its value is
-0.3850 Volts, presume this module is configured to accept
1 Volts input.


(6011/D, 6012/D, 6014D)