ADLINK ND-6018 User Manual

Page 46

Advertising
background image

38

Command Set

Note:

1.

When you want to change the checksum or baud rate, the
DEFAULT* pin must be grounded at first.

2.

Waiting a maximum of 7 seconds to perform auto calibration and
ranging after the analog input module is reconfigured.

Please

don’t execute any other command during this time period.

@Example

User command:

%0130050600<CR>

Response:

!30<CR>

Item Meaning

Description

%

(Leading Code)

Command leading code.

01

(OldAddr)

Original address ID is 01(Hex).

30

(NewAddr)

New address ID is 30(Hex).

05 (InputRange) Analog input range is

±2.5V

06

(BaudRate)

Baud rate is 9600.

00

(DataFormat)

00 means data format is engineering
units, checksum is disable and
integration time is 50 ms (60Hz).

<CR> Carriage

return 0x0D.