ADLINK ND-6018 User Manual
Page 46
Advertising
38
• Command Set
Note:
1.
When you want to change the checksum or baud rate, the
DEFAULT* pin must be grounded at first.
2.
Waiting a maximum of 7 seconds to perform auto calibration and
ranging after the analog input module is reconfigured.
Please
don’t execute any other command during this time period.
@Example
User command:
%0130050600<CR>
Response:
!30<CR>
Item Meaning
Description
%
(Leading Code)
Command leading code.
01
(OldAddr)
Original address ID is 01(Hex).
30
(NewAddr)
New address ID is 30(Hex).
05 (InputRange) Analog input range is
±2.5V
06
(BaudRate)
Baud rate is 9600.
00
(DataFormat)
00 means data format is engineering
units, checksum is disable and
integration time is 50 ms (60Hz).
<CR> Carriage
return 0x0D.