Command Set

3.40 Read Leading Code Setting

@Description

Read command leading code setting and host watchdog status.

@Syntax

~(Addr)0<CR
>

~

Command leading code.

(Addr)

Address ID

0

Read command leading code setting.

@Response

!(Addr)(Status)(C1)(C2)(C3)(C4)(C5)(C6)<CR>

or
?(Addr)<CR
>

!

Command is valid.

?

Command is invalid.

(Addr)

Address ID

(Status) (2-character)

Bit 0: Reserved
Bit 1: Power failure or watchdog failure
Bit 2: Host watchdog is enable
Bit 3: Host failure

(C1)

Leading code 1, for read configuration status,
firmware version, etc. default is $.
(1-character)

(C2)

Leading code 2, for read synchronize sampling,
digital output, default is #.
(1-character)

(C3)

Leading code 3, for change configuration.
default is %. (1-character)

(C4)

Leading code 4, for read alarm status, enable alarm,
etc. default is @. (1-character)

(6011/D, 6012/D, 6013

6014D, 6017, 6018)