3.2. Set Configuration

@Description

Configure the basic setting of NuDAM, including the address ID, output
signal range, baud rate, and data format. The new configuration will be
available after executing the command.

@Syntax

%(OldAddr)(NewAddr)(OutputRange)(BaudRate)(DataFormat)<CR>

%

Command leading code. (1-character)

(OldAddr)

NuDAM module original address ID. The
default address ID of a brand new module is
01. The value range of address ID is 00 to FF
in hexadecimal. (2-character)

(NewAddr)

New address ID, if you don’t want to change
address ID, let new address ID equals to the
old one. (2-character)

(OutputRange)

Define analog output range, refers to Table
3-1 for details. (2-character)

(BaudRate)

Define communication baud rate, refers to
Table 3-2 for details. (2-character)

(DataFormat)

Define checksum, integration time and
output data format, refers to Figure 3-1 for
details. (2-character)

@Response

!(Addr)<CR>

or

?(Addr)<CR>

(Addr)

Address ID.

!

Command is valid.

?

Command is invalid, parameter values are invalid,
or change the setting without grounding the
DEFAULT* pin.

Note : When you want to change the checksum or baud rate, the DEFAULT*

pin must be grounded at first.

@Example