ADLINK ND-6024 User Manual
Page 55
Command Set
• 49
@Example
User command:
~063<CR>
Response:
!061123F0<CR>
06
Address ID
1
Host watchdog timer is enable.
12
Timeout value. 0x12 = 18
18 * 53.3 = 959 ms (Firmware Version 1.x)
18 * 100 = 1800 ms (Firmware Version 2.x)
3F0
0x3F0 is hexadecimal
Analog output value is 4.923 mA for 0-20mA
Analog output value is 4.923 mA for 4-20mA
Analog output value is 2.462 V for 0-10 V
User command:
~063<CR>
Response:
!06112800800800800<CR>
06
Address ID
1
Host watchdog timer is enable.
12
Timeout value. 0x12 = 18
18 * 53.3 = 959 ms (Firmware Version 1.x)
18 * 100 = 1800 ms (Firmware Version 2.x)
800
800
800
800
0x800 is hexadecimal
Analog output value is 0V for port A
Analog output value is 0V for port B
Analog output value is 0V for port C
Analog output value is 0V for port D