3 read configuration – ADLINK ND-6024 User Manual

Page 32

Advertising
background image

26

Command Set

3.3 Read Configuration

@Description

Read the configuration of module on a specified address ID.

@Syntax

$(Addr)2<CR>

$

Command leading code

(Addr)

Address ID.

2

Command code for reading configuration

@Response

!(Addr)(OutputRange)(BaudRate)(DataFormat)<CR>

or

?(Addr)<CR>

!

Command is valid.

?

Command is invalid.

(Addr)

Address ID.

(OutputRange)

Current setting of analog voltage output, refers
to Table 3-1 for details.

(BaudRate)

Current setting of communication baud rate,
refers to Table 3-2 for details.

(DataFormat)

Current settings of checksum, integration time
and output data format, refers to Figure 3-1 for
details.

@Example

User command:

$182<CR>

Response:

!18320610<CR>

!

Command is valid.

18

Address ID.

32

Analog output range is 0 to 10V

06

Baud rate is 9600 bps.

10

The output data is in engineering units, slew rate is
1mA/sec, checksum is disable.