Analog Output Calibration

5

Analog Output Calibration

5.1 Calibration

The NuDAM analog output module needs to be calibrated. It has a factory
default calibration . User can use NuDAM Adminstration utility to do any type of
calibration.

5.2 Analog Output Module Calibration

What do you need to do calibration ?

1. One 5 1/2 digit multimeter.

2. A resistor 250

Ω (Accurary is 0.01 %).

3. NuDAM Aministration Utility.

Calibration Procedure

1. Select output range to 0 ~20 mA or 4~20 mA.

2. Put the resistor 250

Ω to the NuDAM-6021 (+ IOUT (Pin.1) and -IOUT

(Pin.2)).

3.

Put 5 1/2 digit multimeter to measure + IOUT (Pin.1) and -IOUT (Pin.2)
.