3.6 Reset

Status

@Description

Read the reset status of module at specified address to check whether if it
has been reset since the last reset status command was issued to the
module.

@Syntax

$(Addr)5<CR>

$

Command leading code.

(Addr)

Address ID.

5

Reset Status Command.

@Response

!(Addr)(Status)<CR>

or

?(Addr)<CR>

!

Command is valid.

?

Command is invalid.

(Addr)

Address ID.

(Status)

0 : It has not been reset since the last reset
status command was issued.
1 : It has been reset since the last reset
status command was issued.

@Example

User command:

$185<CR>

Response:

!180<CR>

Status is 0 means this digital I/O module has not been reset,

since the last reset status command was issued.