ADLINK ND-6024 User Manual

Page 30

Advertising
background image

24

Command Set

User command:

%0118310610<CR>

Response:

!18<CR>

Item Meaning

Description

%

(Leading Code)

Command leading code.

01

(OldAddr)

Original address ID is 01(Hex).

18

(NewAddr)

New address ID is 18(Hex).

31 (OutputRange) Analog

output range is 4 to 20 mA

06

(BaudRate)

Baud rate is 9600.

10

(DataFormat)

10 means a slew rate is 1.000 mA/sec
and checksum is disable.

<CR> Carriage

return 0x0D.

Code
(Hex)

Signal Range of Output Range

Modules

30

0 to 20 mA

6021

31

4 to 20 mA

6021

32

0 to 10 V

6021

33

-10 to 10 V

6024

Table 0-1 Analog Output Range Setting

Code

Baudrate

03 1200

bps

04 2400

bps

05 4800

bps

06 9600

bps

07 19200

bps

08 38400

bps

Table 3-2 Baud rate setting code