ADLINK ND-6024 User Manual

Page 38

Advertising
background image

32

Command Set

3.9 Digital Input (6024 only)

@Description

Read the digital input channel value.

@Syntax

$(Addr)8<CR>

$

Command leading code.

(Addr)

Address ID

8

Digital data input command.

@Response

!(DataIn)0000<CR>

or

?(Addr)<CR>

!

Command is valid.

?

Command is invalid.

(DataIn)

Value of digital input. (2-character)

@Example

User command:

$308<CR>

Response:

!320000<CR>

!

Command is valid.

32

32 (00110010) means digital output channel 1, 4, 5
are ON, channel 0, 2, 3, 6 are OFF.

0000

No used

Advertising